Flair offers top-notch solutions for power factor control and filtering, positioning itself as a leading manufacturer in China. Our PFC capacitors are available as capacitor banks, equipped with advanced protection devices against overheating, overcurrent, and overpressure. Designed to cater to various needs, our capacitors can be configured for single-phase or three-phase systems. Shunt capacitors play a crucial role in compensating for reactive power in power systems, enhancing the power factor to significantly improve power quality. Additionally, our filter capacitors effectively eliminate frequency harmonics in power systems, ensuring optimal performance. As a trusted supplier and factory, Flair is dedicated to providing high-quality products that meet industry standards and exceed customer expectations.

    Flair Shunt Capacitor Design Features

    1

    Dielectric: Metalized film

    2

    Filling Material: Heat convertible resin

    3

    Safety Protection: Each element is mounted with a safety protection device to protect the capacitor from explosion or short-circuit failures, ensuring failure elements are separated from circuits.

    4

    Discharge Resistor: Built-in discharge resistor available

    5

    Package: Stainless steel shell, hermetically sealed

    6

    Frequency: 50Hz

    7

    Shell Construction: 1mm galvanized stainless steel shell with good heat dissipation effect

    8

    Spacing Design: Sufficient space between elements, beneficial for heat dissipation and lowering internal temperature

    9

    Fuse Protection: Internal fuse available

    10

    Busbar: Internal copper busbar connection (low current density, low contact resistance, low loss)

    11

    Safety Discharge: Fixed connection discharge resistor (decreases voltage below 75V within 3 minutes after power cut-off, upon request)

    12

    Environment Temperature: -20°C ~ +50°C

    13

    Altitude: Below 2000m

    Flair Shunt Capacitor Design Features Overview

    Specification Table

    Model Capacity Current Capacitance Weight Dimension (mm)
    Kvar A μF kg Length Width Height
    3-phase 400VAC 50Hz Indoor
    FACS-BC3 25 20.8×3 166×3 5.0 200~240 112 242
    FACS-BC3 30 25.0×3 199×3 5.0 200~240 112 242
    FACS-BC3 40 33.3×3 265×3 6.5 200~240 112 306
    FACS-BC3 50 41.7×3 332×3 7.8 200~240 112 370
    FACS-BC3 60 50.0×3 398×3 9.0 200~240 112 435
    3-phase 460VAC 50Hz Indoor
    FACS-BC3 20 14.5×3 100×3 4.2 200~240 112 178
    FACS-BC3 25 18.1×3 125×3 5.0 200~240 112 242
    FACS-BC3 30 21.7×3 150×3 5.0 200~240 112 242
    FACS-BC3 40 29.0×3 201×3 6.5 200~240 112 306
    FACS-BC3 50 36.2×3 251×3 7.8 200~240 112 370
    FACS-BC3 60 43.5×3 301×3 9.0 200~240 112 435
    Note: The capacitor internal is not connected; Generally used for capacitor triangle connection angle in the fling-cut switch.
    FACS-BC3 Technical Diagram
    Model Capacity Current Capacitance Weight Dimension (mm)
    Kvar A μF kg Length Width Height
    3-phase 400VAC 50Hz
    FACS-BC3Y 6 8.7 119 3.6 200~240 112 114
    FACS-BC3Y 12 17.3 239 4.3 200~240 112 178
    FACS-BC3Y 18 26.0 358 5.1 200~240 112 242
    FACS-BC3Y 24 34.6 477 6.5 200~240 112 306
    FACS-BC3Y 30 43.3 597 7.8 200~240 112 370
    FACS-BC3Y 36 52.0 716 9.1 200~240 112 435
    3-phase 440VAC 50Hz
    FACS-BC3Y 7 9.2 115 3.6 200~240 112 114
    FACS-BC3Y 14 18.4 230 4.3 200~240 112 178
    FACS-BC3Y 21 27.6 345 5.1 200~240 112 242
    FACS-BC3Y 29 38.1 477 6.5 200~240 112 306
    FACS-BC3Y 36 47.2 592 7.8 200~240 112 370
    FACS-BC3Y 43 56.4 707 9.1 200~240 112 435
    Note: The capacitor internal is wye connection;
    FACS-BC3Y Technical Diagram
    Model Capacity Current Capacitance Weight Dimension (mm)
    Kvar A μF kg Length Width Height
    3-phase 400VAC 50Hz Indoor
    FACS-BC 20 28.9 398 4.2 200~240 112 178
    FACS-BC 25 36.1 497 5.0 200~240 112 242
    FACS-BC 30 43.3 597 5.0 200~240 112 242
    FACS-BC 40 57.7 796 6.5 200~240 112 306
    FACS-BC 50 72.2 995 7.8 200~240 112 370
    FACS-BC 60 86.6 1194 9.0 200~240 112 435
    3-phase 460VAC 50Hz Indoor
    FACS-BC 20 25.1 301 4.2 200~240 112 178
    FACS-BC 25 31.4 376 5.0 200~240 112 242
    FACS-BC 30 37.7 451 5.0 200~240 112 242
    FACS-BC 40 50.2 602 6.5 200~240 112 306
    FACS-BC 50 62.8 752 7.8 200~240 112 370
    FACS-BC 60 73.3 903 9.0 200~240 112 435
    Note: The harmonic filtering capacitor is usually connect with reactor in series to filter the frequency harmonic in the power system;
    FACS-BC Technical Diagram

    Frequently Asked Questions (FAQ)

    Q1: What are the main dielectric and filling materials used in these shunt capacitors?

    Flair shunt capacitors utilize high-grade metalized film as the dielectric material and are encapsulated with heat-convertible resin inside a hermetically sealed stainless steel shell.

    Q2: How does the internal safety protection mechanism work?

    Each element is equipped with an individual safety protection device and internal fuse. In the event of a fault, the failed element is promptly isolated from the circuit to prevent explosion or short-circuit hazards.

    Q3: How quickly does the discharge resistor lower the terminal voltage?

    With the fixed-connection discharge resistor installed, the residual voltage is reduced below 75V within 3 minutes after power disconnection (available upon request).

    Q4: What internal connection configurations are available for different series?

    The FACS-BC3 model features non-connected internal elements suitable for delta configurations via fling-cut switches, the FACS-BC3Y provides an internal wye (star) connection, and the FACS-BC model is designed for standard 3-phase systems.

    Q5: Can these capacitors be used in harmonic filtering applications?

    Yes, the FACS-BC series harmonic filtering capacitors can be connected in series with detuned or tuning reactors to effectively filter frequency harmonics in power networks.

    Q6: What are the standard operating temperature and altitude ratings?

    The capacitors are rated for an ambient operating temperature range of -20°C to +50°C and can operate at altitudes below 2000 meters.